EasyManua.ls Logo

Siemens RS-485 - Device Data and Remote Operation; Remote Operation Parameters

Siemens RS-485
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10/14
Siemens Building Technologies CC1A7865.1en
HVAC Products 31.10.2002
Address Data
type
Access Parameter Value range Default
value
0x0300 word [13] R / O Device data
0x0300 char SWVersion [11+1] Software version
0x0306 char VDNNr [13+1] VdN number
Address Data
type
Access Parameter Value range Default
value
0x0400 float R / O TEMP Actual value E3 (unfiltered)
0x0500 word R / W REM Activation remote operation 0...2 * 0
0x0501 word R / W ROFF Controller OFF in REMOTE
SETPOINT
0...1 ** 0
0x0502 float R / W RHYS1 Switch-on threshold REMOTE 0...-1999 HYS1
0x0504 float R / W RHYS2 Switch-off threshold bottom
REMOTE
0...RHYS3 HYS2
0x0506 float R / W RHYS3 Switch-off threshold top REMOTE 0...9999 HYS3
0x0508 float R / W SPR Setpoint REMOTE SPL...SPH SP1
0x050A word R / W RK1 Burner control remote operation 0...1 0
0x050B word R / W RK2 Relay K2 remote operation 0...1 0
0x050C word R / W RK3 Relay K3 remote operation 0...1 0
0x050D word R / W RK6 Relay LK remote operation 0...1 0
0x050E word R / W RSTEP Step control remote operation -100...100 0
0x050F float R / W RY Positioning output remote
operation
0...100 0
* 0 = local ** 1 = controller OFF
1 = remote setpoint
2 = fully remote
Device data
Remote operation