21/166
Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Handling 15.07.2002
2.4.1 Overview of enduser parameters
Line Function Range Unit Resolution Factory
setting
Setting the clock
1 Time of day 0...23:59 h / min 1 min -
2 weekday 1...7 Weekday 1 day -
3 Date (day, month) 01.01...31.12 dd.MM 1 -
4 Year 1999...2099 jjjj 1 -
Time switch program for heating circuit
5 Weekday-preselection heating circuit
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Weekday 1 day -
6 Switch-on time 1. 3
rd
period heating circuit 00:00...23:59 h / min 10 min 06:00
7 Switch-off time 1. 3
rd
period heating circuit 00:00...23:59 h / min 10 min 22:00
8 Switch-on time 2. 3
rd
period heating circuit 00:00...23:59 h / min 10 min - -:- -
9 Switch-off time 2. 3
rd
period heating circuit 00:00...23:59 h / min 10 min - -:- -
10 Switch-on time 3. 3
rd
period heating circuit 00:00...23:59 h / min 10 min - -:- -
11 Switch-off time 3. 3
rd
period heating circuit 00:00...23:59 h / min 10 min - -:- -
D.h.w. values
13 Nominal setpoint of the d.h.w. temperature (TBWw)
TBWR Line 120
TBWmax Line 40 (OEM)
TBWR...TBWmax °C 1 55
Heating circuit values
14 Reduced room temperature setpoint (TRRw)
TRF Line 15
TRN Setpoint knob
TRF...TRN °C 0,5 16
15 Frost protection setpoint of the room temperature
(TRFw)
TRR Line 14
4...TRR °C 0,5 10
16 summer / winter changeover temperature 8...30 °C 0,5 17
17 heating curve slope
-:- - Inactive
2,5...40 Active
-:- - / 2,5...40 - 0,5 15
Actual values
18 Actual value of the room temperature (TRx) 0...50 °C 0,5 -
19
Actual value of the outside temperature (TAx)
To set the attenuated outside temperature to Tax, press the + / -
buttons simultaneously for 3 seconds.
-50...+50 °C 0,5 -
Maintenance
23 Standard time program for heating circuit and d.h.w.
To activate, press the + and - buttons simultaneously for 3 seconds
0/1 - 1 0
Time switch program for d.h.w. heating
29 preselection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Weekday 1 day -
30 Switch-on time 1. 3
rd
period d.h.w. 00:00...23:59 h / min 10 min 06:00
31 Switch-off time 1. 3
rd
period d.h.w. 00:00...23:59 h / min 10 min 22:00
32 Switch-on time 2. 3
rd
period d.h.w. 00:00...23:59 h / min 10 min - -:- -
33 Switch-off time 2. 3
rd
period d.h.w. 00:00...23:59 h / min 10 min - -:- -
34 Switch-on time 3. 3
rd
period d.h.w. 00:00...23:59 h / min 10 min - -:- -
35 Switch-off time 3. 3
rd
period d.h.w. 00:00...23:59 h / min 10 min - -:- -
Service
49 Indication of BMU error code
1...4 = BMU number, 1...255 = error code
1...4 / 0...255 - 1 -
50 indication of faults 0..255 / 00.01–14.16 - 1 -