Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Description of the enduser settings 15.07.2002
Entry:
– – : – – Switching point inactive
00:00...24:00 At the time entered, heating to the respective temperature is ensured.
Line
Switching point Temperature setpoint Standard
Switch-on time period 1 Setpoint of knob
06:00
Switch-off time period 1 Reduced setpoint
22:00
Switch-on time period 2 Setpoint of knob
– – : – –
Switch-off time period 2 Reduced setpoint
– – : – –
Switch-on time period 3 Setpoint of knob
– – : – –
Switch-off time period 3 Reduced setpoint
– – : – –
When using a QAA70 room unit, the heating program will be acted upon. However, this
works only if operating mode “AUTO” is selected on the controller.
Program overview
Effect of room unit