Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Description of the enduser settings 15.07.2002
D.h.w. values
3.11 Nominal d.h.w. temperature setpoint
D.h.w. heating only if there is a demand for it
Possibility of using 2 different d.h.w. temperature setpoints
1. Press the operating line selection buttons to select line 13.
2. Press the + / – buttons to adjust the nominal setpoint of the d.h.w. temperature.
Setting range Unit Factory setting
TBWR...TBWmax °C 55
TBWR Reduced setpoint of d.h.w. temperature (setting on operating line 120)
TBWmax Maximum nominal setpoint of d.h.w. temperature (setting on line 40
OEM
)
0 10 20 30 40 50 60 70 80 90 100 120 130 140 °C
2379Z16
The temperature setpoint during normal d.h.w. operation will be changed.
13 Setting "Nominal setpoint of the d.h.w. temperature”
120 Setting "Reduced setpoint of the d.h.w. temperature”
40
OEM
Setting "Maximum nominal setpoint of the d.h.w. temperature”
D.h.w. heating has 2 different setpoints that can be used:
Nominal d.h.w. temperature setpoint: It ensures the d.h.w. temperature required
during main occupancy times
Reduced d.h.w. temperature setpoint (setting on operating line 120): it ensures the
d.h.w. temperature required during the main occupancy times.
The criteria required for releasing d.h.w. heating are defined by the settings made on
lines 121 and 123 and 124.
In the event of a sensor with a short-circuit (display ”- - -” in input test, test step 1) the
d.h.w. will not be heated (protection against scalding).