Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Description of the enduser settings 15.07.2002
1. Press the line selection buttons to select line 30 to 35.
2. Press the + / – buttons to set the switching time on each line.
Setting range Unit Factory setting
- -:- -...24:00 h : min
See "Program overview"
below
First, select the weekday for which the switching times shall be entered!
The controller then makes a check to ensure the entries have been made in the correct
order.
At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
Entry:
– : – – Switching point inactive
00:00...24:00 At the time entered, the d.h.w. will be heated to the respective
temperature.
Line
Switching point D.h.w temperature setpoint Standard
Switch-on time period 1
Nominal setpoint
06:00
Switch-off time period 1
Reduced setpoint
22:00
Switch-on time period 2
Nominal setpoint
– – : – –
Switch-off time period 2
Reduced setpoint
– – : – –
Switch-on time period 3
Nominal setpoint
– – : – –
Switch-off time period 3
Reduced setpoint
– – : – –
Setting
• • •
! Important
Note
Effect
Program overview