4.11 Composite outside temperature
• Compensating variable for the flow temperature control
The composite outside temperature is a mixture of the actual outside temperature and
the attenuated outside temperature calculated by the controller.
This operating line automatically displays the actual value [°C] of the composite outside
temperature. No direct setting can be made.
Display Unit
-50...50 °C
The mixture of actual and attenuated outside temperature is dependent on the type of
building construction (setting 105) and is generated as follows:
Selected type of construction Composite outside temperature
Heavy (setting 105 = 0) Tagem = ½ TAakt + ½ TAged
Light (setting 105 = 1) Tagem = ¾ TAakt + ¼ TAged
The composite outside temperature as a compensating variable acts on flow
temperature control, that is thus matched to the prevailing weather conditions.
It also acts on the 24-hour heating limit to shut down the heating.
13
14
15
16
17
2371D12
18:00 06:00 06:00 18:0018:00
t
TA
TAakt
TAged
°C
TAgem1
TAgem0
TAakt Actual outside temperature
TAged Attenuated outside temperature
TAgem1 Composite outside temperature for light building structures
TAgem0 Composite outside temperature for heavy building structures