Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E
HVAC Products Description of the heating engineer settings 15.07.2002
Heating circuit values
4.27 Parallel displacement of the heating curve
Adjustment of controller's temperature scale to the actual plant conditions.
Produces a parallel displacement of the heating curve in order to achieve a better
match of room temperature setpoints and actual room temperatures.
1. Press the operating line selection buttons to select operating line 100.
2. Press the + / – buttons to set the parallel displacement..
Setting range Unit Factory setting
-4.5...+4.5 °C (K) 0.0
By changing the value entered, all room temperature setpoints will be appropriately
raised or lowered. This allows the room temperature setpoints to be matched to the
effective room temperatures.
If a nominal room temperature setpoint of 20 °C adjusted on the controller always
produces a room temperature of 22 °C (independent of the prevailing outside
temperature), displace the heating curve downward by 2 °C.
Each setpoint readjustment, be it by changing the setting value or the operational level,
corresponds to a parallel displacement of the heating curve.
20 10 0 -10 -20
-30
90
80
70
60
50
40
30
°C
°C
2406D02
100
0
10
10
0
30
T
R
w
TA
TV
TV Flow temperature
TA Composite outside temperature
TRw Room temperature setpoint
4.28 Room influence
More accurate room temperature control due to temperature checkback signal from
the space
Use of heat gains
Possibility of boost heating and quick setback
Benefit
Description
Setting
Effect
Example:
Parallel displacement
Benefit