116/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.48 Range of action of central changeover
The range of action of central changeover can be defined.
Function for defining the range of action of central changeover.
Setting range Unit Factory setting
0 / 1 Increment 1
The range of action can be defined for central changeover “Changeover of operating
mode” (HCs + d.h.w., HCs), “Summer / winter changeover” and “Stand-by”. The range
of action can be defined by making the following settings:
0 Changeover takes place with all controllers in the same segment.
1 Changeover takes place with all controllers in the entire system (LPB).
The setting is of importance only if the controller is defined as the master and located in
segment 0 (address 0/1). With any other addressing, it has no effect.