1.25 Number of burner starts stage 2
Auxiliary value for ascertaining the average burner running time.
Display Unit
0...65535 Number
The number of starts of burner stage 2 will automatically be displayed on this line.
The number of starts of burner stage 2 are counted with the signal received from output
K5. Display of the number of burner starts is updated each time the burner is started
up.
The number of burner starts is written to non-volatile memory at 2-hour intervals or
whenever there is a power failure.
Description
Setting
Effect
Counting