Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
Setpoints
2.13 Display of boiler temperature setpoint
Indication of boiler temperature setpoint.
Better overview of the plant’s operating state.
The current boiler temperature setpoint will automatically be displayed on this line.
Display Unit
0...140 °C
The setpoint can only be displayed, but not changed. The function helps better
understand the control sequences taking place in the controller.
No setpoint is displayed (---) when there is no heat demand from the consumers.
2.14 Display of common flow temperature
setpoint
Display of common flow temperature setpoint.
Better overview of the plant’s operating state.
The current common flow temperature setpoint will automatically be displayed on this
line.
Display Unit
0...140 °C
The setpoint can only be displayed, but not changed. The function helps better
understand the control sequences taking place in the controller.
No setpoint is displayed (---) when there is no heat demand from the consumers.
Benefits
Description
Setting
Benefits
Description
Setting