EasyManua.ls Logo

Siemens RVA53.280 - Heating Circuit; Parallel Displacement of Heating Curve

Siemens RVA53.280
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
83/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
Heating circuit
2.23 Parallel displacement of heating curve
Readjustment of room temperature setting, especially in plants without room sensor.
Produces a parallel displacement of the heating curve in order to achieve a better
match of heat generation and heat consumption.
Setting range Unit Factory setting
-4.5...+4.5 °C (K) 0.0
By changing the value entered, all room temperature setpoints will be appropriately
raised or lowered. This allows the room temperature setpoints to be matched to the
effective room temperatures.
If a nominal room temperature setpoint of 20 °C adjusted on the controller always
produces a room temperature of 22 °C, displace the heating curve downward by 2 °C.
Each setpoint readjustment, be it via the setting value or the operational level, is a
parallel displacement of the heating curve.
20 10 0 -10 -20
-30
90
80
70
60
50
40
30
°C
°C
2406D02
100
0
10
10
0
30
T
R
w
TA
TV
TV Flow temperature
TA Composite outside temperature
TRw Room temperature setpoint
Benefit
Description
Setting
Effect
Example
Parallel displacement

Table of Contents

Related product manuals