110/218
Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of heating engineer settings 26.03.2001
4.48 Floor curing HK1
The floor curing function ensures controlled drying of the floor.
• Observe the relevant standards and regulations of the floor manufacturer!
• Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)!
If not observed, the floor might get damaged!
The floor curing function maintains the flow temperature at a predefined temperature
profile with the help of the mixing valve.
Setting range Unit Factory setting
0...3 – 0
Selection of a temperature profile activates the floor curing function and the heating
circuit ensures the preset flow temperatures.
0 Inactive
1 Functional heating
2 Floor curing heating
3 Functional and floor curing heating
4.48.1 Temperature profile
The following graph shows the temperature profile of the selected floor curing function.
50
45
40
35
30
20
5 10 15 18
[Tag]
0
25
55
Fh
Bh
1 15 7
X