189/218
Siemens Building Technologies Basic Documentation RVA53.242, RVA53.242 CE1P2373E
Landis & Staefa Division General control processes 26.03.2001
TKx
2371Z64
TKw
Control action of modulating burner too slow
TKx Actual value of the boiler temperature
TKw Boiler temperature setpoint
Procedure
1. Reduce Xp in steps of about 25 % of the previous value.
2.
Reduce Tv in steps of 1 to 2 seconds (if value 0 is reached, the controller
operates as a PI controller)
3. Reduce Tn in steps of 10 to 20 seconds
Repeat steps 2 and 3 alternately.
1.1.2 Control action too fast
If the control system’s response is too “hefty” so that it starts oscillating, setting
parameters Xp, Tn and Tv must be increased in a stepwise fashion. A new
readjustment should be made only after the control action resulting from the previous
readjustment is completed.
TKx
2371Z65
TKw
Control action of modulating burner too fast
Procedure
1. Increase Xp in steps of about 25 % of the previous value.
2. Increase Tv in steps of 2 to 5 seconds.
3. Increase Tv in steps of 10 to 20 seconds.
Repeat steps 2 and 3 alternately.
If not sufficient:
If not sufficient: