Siemens Building Technologies Basic Documentation RVA63.242, RVA53.242 CE1P2373E
Landis & Staefa Division Description of end-user settings 26.03.2001
3.28 Number of burner starts stage 2
Auxiliary value for ascertaining the average burner running time.
Display Unit
0...65535 Number
The number of starts of burner stage 2 will automatically be displayed on this line.
The number of starts of burner stage 2 are counted with the signal received from output
K5. But this is the case only when voltage is present at E1. Display of the number of
burner starts is updated each time the burner is started up.
The number of burner starts is written to non-volatile memory at 2-hour intervals or
whenever there is a power failure.
Description
Setting
Effect
Counting