3.14 Boost of room temperature setpoint
(DTRSA)
Reduction of the building’s heating up time.
This setting is active only if a room sensor is used.
Setting range Unit Factory setting
0...20 °C (K) 5
The duration of boost heating will be changed.
Entry:
Increase: More setpoint boost
Heating up time will become shorter
Decrease: Less setpoint boost
Heating up time will become longer
3.14.1 Boost heating
Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
With the setting on line 33
OEM
, the room temperature setpoint will be raised until the
room is heated up (TRw - ¼ °C).
The boost produces an increase in the flow temperature setpoint.