22/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.4.1 Overview of end-user parameters
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
Setting the clock
1 1 Time of day 0...23:59 h / min 1 min 00:00
2 2 Weekday 1...7 Day 1 day 1
3 3 Date (day, month) 01.01...31.12 tt.MM 1 -
4 4 Year 1999...2099 jjjj 1 -
Time switch program 1
5 5 Pre-selection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day 1 day -
66
Switch-on time 1. Period
- -:- -...24:00 h / min 10 min 06:00
77
Switch-off time 1. Period
- -:- -...24:00 h / min 10 min 22:00
88
Switch-on time 2. Period
- -:- -...24:00 h / min 10 min - -:- -
99
Switch-off time 2. Period
- -:- -...24:00 h / min 10 min - -:- -
10 10
Switch-on time 3. Period
- -:- -...24:00 h / min 10 min - -:- -
11 11
Switch-off time 3. Period
- -:- -...24:00 h / min 10 min - -:- -
Time switch program 3 (d.h.w.)
19 19 Pre-selection of weekday
1-7 7-day block
1...7 Individual days
1-7 / 1...7 Day 1 day -
20 20 Switch-on time 1. Period - -:- -...24:00 h / min 10 min 06:00
21 21 Switch-off time 1. Period - -:- -...24:00 h / min 10 min 22:00
22 22 Switch-on time 2. Period - -:- -...24:00 h / min 10 min - -:- -
23 23 Switch-off time 2. Period - -:- -...24:00 h / min 10 min - -:- -
24 24 Switch-on time 3. Period - -:- -...24:00 h / min 10 min - -:- -
25 25 Switch-off time 3. Period - -:- -...24:00 h / min 10 min - -:- -
D.h.w.
26 26 Nominal setpoint of d.h.w. temperature (TBWw)
TBWRw Line 120
TBWmax Line 50 (OEM)
TBWR...TBWmax °C 1 55
Heating circuit
27 27 Reduced setpoint of room temperature
(TRRw)
TRF Frost protection setpoint of room temperature,
line 28
TRN Setpoint knob heating circuit 1 or 2
TRF...TRN °C 0,5 16
28 28 Frost protection setpoint of room temperature
(TRFw)
TRRw Line 27
4...TRRw °C 0,5 10
29 29 Summer / winter changeover temperature
(THG)
8...30 °C 0,5 17
30 30 Slope of heating curve (S)
- : - - Inactive (only HC2)
2.5...40 Active
- : - - / 2,5...40 - 0,5 15
33 33 Actual value of room temperature (TRx) 0...50 °C 0,5 -
34 34 Actual value of outside temperature (TAx)
To reset the attenuated outside temperature to TAx, press the
+ and - buttons simultaneously for 3 seconds.
-50...+50 °C 0,5 -