26/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
77 - Floor curing data
Day
Flow temperature setpoint
0...32
0...95
-
°C
1-
Heat generating equipment
80 80 Type of heat source
0 No heat generation or PPS-BMU
1 Single-stage burner
2 2-stage burner
0...2 - 1 2
81 81 Minimum limitation of boiler temperature (TKmin)
Tkmin
OEM
Line 1 OEM
Tkmax Line2OEM
TKmin
OEM
...TKmax °C 1 40
82 82 Extra heating for the bathroom
(HK2 ist pump heating circuits)
0Inactive
1Active
0/1 - 1 0
Heating circuit
100 100 Parallel displacement of heating curve -4,5...+4,5 °C (K) 0,5 0,0
101 101 Room influence
0Inactive
1Active
0/1 - 1 1
102 102 Switching differential of the room temperature
(SDR)
--.- Inactive
0.5...4.0 Active
- -:-...4,0 °C (K) 0,5 - -:-
103 103 Operating mode of room unit
0 Parallel action: Room unit 1 on heating circuit 1
Room unit 2 on heating circuit 2
1 Crossed action: Room unit 1 on heating circuit 2
Room unit 2 on heating circuit 1
2 Serial action: Room unit 1 on heating circuits 1
and 2
0...2 - 1 0
104 104 Room unit values
0 Parallel action: Room unit 1 on heating circuit 1
Room unit 2 on heating circuit 2
1 Crossed action: Room unit 1 on heating circuit 2
Room unit 2 on heating circuit 1
2 Serial action: Room unit 1 on heating circuits 1
and 2
0...2 - 1 0
105 105 Minimum limitation of flow temperature setpoint
(TVmin)
TVmax Line 107
8...TVmax °C 1 8
107 107 Maximum limitation of flow temperature setpoint
(TVmax)
Tvmin Line 105
TVmin...95 °C 1 80
109 109 Maximum forward shift of optimum start control
0 forwardshift/OFF
00:00...06:00 hh:mm 10 min 00:00
110 110 Maximum forward shift of optimum stop control
0 Noforwardingshift
00:00...06:00 hh:mm 10 min 00:00
113 113 Type of building construction
0Heavy
1 Light
0/1 - 1 1
114 114 Adaption of heating curve
0Inactive
1Active
0/1 - 1 1
115 115 Gain of locking signal 0...200 % 1 100