27/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
RVA63.280
RVA53.280
Function
Range
Unit
Resolution
Factory setting
116 - Floor curing
0Off
1 Functional heating
2 Floor curing
3 Functional and floor curing heating
0...3 - 1 0
D.h.w.
120 120 Reduced setpoint of d.h.w. temperature (TBWR)
TBWw Line 26
8...TBWw °C 1 40
121 121 D.h.w. heating program
0 24 h/day
1 Heating program with forward shift
2 Timeswitchprogram3
0...2 - 1 1
123 - Assignment of d.h.w. heating
0 Local heating circuit
1 All heating circuits in the segment
2 All heating circuits in the system
0...2 - 1 2
124 124 D.h.w. charging
0 Once per day with a forward shift of 2.5 hours
1 Severaltimesperdaywitha1hforwardshift
0/1 - 1 1
125 125 Type of d.h.w. demand
0Sensor
1 Control thermostat
0/1 - 1 0
126 126 Boost of the flow temperature setpoint for d.h.w.
heating (UEBW)
0...30 °C (K) 1 16
127 127 D.h.w. priority
0 Absolute (mixing and pump heating circuit)
1 Shifting (mixing and pump heating circuit)
2 None (parallel)
3 Mixing heating circuit (shifted)
Pump heating circuit (absolut)
0...3 - 1 1
128 128 Controlling element for d.h.w.
0 Charging pump
1 Diverting valve
0/1 - 1 0
LPB / system
140 - LPB device address
0 Standalone
1...16 Device address (system)
0...16 - 1 0
141 - LPB segment address
0 Heat source segment
1...14 Heat consumption segments
0...14 - 1 0
142 - LPB power supply
0 Off (central bus power supply
1) Auto (bus power supply via controller)
0/1 - 1 1
143 - Display of LPB power supply On / OFF - -
145 - Range of action of central changeover
0 In the segment
1 In the system (if segment address = 0)
0/1 - 1 1
146 - Automatic summer / winter changeover
0 Local changeover
1 Central changeover of all heating circuits
0/1 - 1 0
147 - Central stand-by switch
1)
0Off
1ON
0/1 - 1 0
148 - Clock mode
0 Autonomous clock
1 System time without adjustment
2 (System time with adjustment)
3 System clock (master)
0...3 - 1 0