51/184
Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
D.h.w. values
1.15 Nominal setpoint of d.h.w. temperature
(TBWw)
D.h.w. heating only if there is demand for it.
Possibility of using 2 different d.h.w. temperature setpoints.
Setting range Unit Factory setting
TBWR...TBWmax °C 55
TBWR Reduced setpoint of d.h.w. temperature (setting on line 120)
TBWmax Maximum nominal setpoint of d.h.w. temperature (setting on line 50
OEM
)
The temperature setpoint during normal d.h.w. operation will be changed.
0102030405060708090100°C
2373Z13
26 Setting "Nominal setpoint of d.h.w. temperature”
120 Setting "Reduced setpoint of d.h.w. temperature”
50
OEM
Setting "Maximum nominal setpoint of d.h.w. temperature”
D.h.w. heating has 2 different setpoints that can be used:
Nominal setpoint of d.h.w. temperature: It ensures the d.h.w. temperature required
during main occupancy times
Reduced setpoint of d.h.w. temperature (setting on line 120): It ensures the d.h.w.
temperature required outside main occupancy times
The times at which these d.h.w. setpoints shall apply can be set with the d.h.w.
program on line 121.
Benefit
Setting
Effect
D.h.w. temperature
setpoints
D.h.w. program