Siemens Building Technologies Basic Dokumentation RVA63.280, RVA53.280 CE1P2374E
Landis & Staefa Division 19.04.2001
2.15 Display of d.h.w temperature setpoint
Indication of d.h.w. temperature setpoint.
Better overview of the plant’s operating state.
The current d.h.w. temperature setpoint will automatically be displayed on this line.
Display Unit
0...140 °C
The setpoint can only be displayed, but not changed.
The value displayed depends on the following parameters:
Current time of day (operating line 1)
Time switch program d.h.w. heating (operating lines 19...35)
Nominal setpoint of d.h.w. temperature
(operating line 26)
Reduced setpoint of d.h.w. temperature
(operating line 120)
Release of d.h.w. heating
(operating line 121)
Assignment of d.h.w.
(operating line 123)
Number of d.h.w. heating cycles per day (operating line 124)
Legionella function ON / OFF (operating line 52
OEM
)
Legionella setpoint (operating line 53
OEM
)
No value (---) is displayed in the following situations:
No d.h.w. heating available
D.h.w. heating is switched off (button for d.h.w. heating OFF or holidays)
Benefits
Description
Setting
Generation of setpoint
Note