2.28 Minimum limitation of flow temperature
setpoint (TVmin)
Prevents too low flow temperatures.
Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
Setting range Unit Factory setting
8...TVmax °C 8
TVmax Maximum limitation of flow temperature setpoint (setting on line 107)
The setting will make certain that the flow temperature setpoint will not fall below a
minimum level.
0102030405060708090100
TV
max
min
akt
°C
2373Z15
TVw
TVw Current flow temperature setpoint
65 Minimum limitation of flow temperature setpoint
70 Maximum limitation of flow temperature setpoint
If the flow temperature setpoint demanded by the heating circuit reaches the minimum
limit and the outside temperature rises, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to fall below it.
Benefit
Description
Setting
Effect
Limitation