97/118
Siemens Building Technologies Basic Documentation RVL471 CE1P2524E
HVAC Products 27 Communication 23.10.2002
Overriding the heating circuits operating mode
Readjustment of room temperature setpoints
Readjustment of the NORMAL d.h.w temperature setpoint
Readjustment of room temperature
Entry of weekday and time of day
Overriding the heating program
Display of the actual values acquired by the RVL471
For this purpose, the QAW70 has the following operating elements:
Operating mode button
Economy button (also called presence button)
Knob for room temperature readjustments
Buttons for selecting the operating lines
Buttons for changing the values
From the QAW70, the heating circuits operating mode of the RVL471 can be overrid-
den. This is accomplished with the operating mode button and the economy button.
To enable the room unit to act on the RVL471, the following operating conditions must
be satisfied:
AUTO mode for heating circuit
No holiday period active, no manual operation
The impact of the QAW70's operating mode button on the RVL471 is as follows:
Operating mode
QAW70
Heating circuits operating mode RVL471
; temporary overriding with economy button possible
Continuously NORMAL or continuously REDUCED
heating, depending on the economy button
STANDBY
With the knob of the QAW70, the room temperature setpoint of NORMAL heating can
be readjusted by ±3 °C.
The adjustment of the room temperature setpoint on the controller's operating line 1 will
not be affected by the QAW70.
If 1 (slave with no remote operation) is entered on operating line 178 ("Source of time
of day") of the RVL471, the time of day on the QAW70 cannot be changed.
Operating
line of the
QAW70
Function, parameter Effect on RVL471, notes
1 Setpoint of NORMAL heating Changes operating line 1 on the RVL471
2 Setpoint of REDUCED heat-
ing
Changes operating line 2 on the RVL471
3 D.h.w temperature setpoint Changes operating line 14 on the RVL471
with plant types with d.h.w. heating
4 Weekday (entry of heating
program)
Corresponds to operating line 4 on the
RVL471
5 1. Third heating period, start
of NORMAL heating
Changes operating line 5 on the RVL471
6 1. Third heating period, start
of REDUCED heating
Changes operating line 6 on the RVL471
7 2. Third heating period, start
of NORMAL heating
Changes operating line 7 on the RVL471
Overriding the heating
circuits operating mode
Knob for room tempera-
ture readjustments
Effect of individual
QAW70 operating lines
on the RVL471