7. Underfloor and ceiling heating systems:
The limit thermostat must be set to the correct value. During the functional test, the flow
temperature may not exceed the maximum permissible level (usually 55 °C). If it does, pro-
ceed immediately as follows:
Either close the valve manually, or
Switch off the pump, or
Close the pump isolating valve
8. Switch on power. The display must show something (e.g. the time of day). If not, the reason
may be one of the following:
No mains voltage present
Main fuse blown
Main switch not set to ON
General information about operation
Setting elements:
– Heating curve
– Setting knob
Display; one operating line is assigned to each setting
Buttons for selecting and readjusting the values:
Selecting the next operating line below
Selecting the next operating line above
Decreasing the displayed value
Increasing the displayed value
Adopting a setting value:
The setting value is adopted by selecting the next operating line (or: Press Info button or one
of the operating mode buttons)
Entering --.- or --:-- :
Press
or until the required display appears
Block jump function:
To select a single operating line quickly, two button combinations can be used:
Press
and for selecting the next line block above
Press
and for selecting the next line block below