Building Technologies 74 319 0618 0 a 17.04.2008 58/276
en
166 Resulting heating
curve
Display function Setpoint incl. setting knob position
and setting on operating line 72
Left: Flow setpoint at 15 °C out-
side temperature
Right: Flow setpoint at –5 °C
outside temperature
167 Outside temp. for
frost protection for
the plant
2.0 °C
(--.- / 0…25)
...................°C
Setting --.- = no frost protection for
the plant
168 Flow temp. setpoint
for frost protection
for the plant
15 °C
(0…140)
...................°C
169 Device number
0
(0…16)
.........................
Data bus address (LPB)
0 = device with no bus
170 Segment number
0
(0…14)
.........................
Data bus address (LPB)
171 Flow alarm
--:-- h
(--:-- / 1:00…10:00)
......................h
Period of time during which the
flow / boiler temperature (sensor
at terminal B1) may stay outside
the limit values
--.-- = function deactivated
Space heating mode D.h.w.
0 = PROTECTION OFF
1 = AUTO OFF
2 = REDUCED OFF
3 = NORMAL OFF
4 = PROTECTION ON
5 = AUTO ON
6 = REDUCED ON
7 = NORMAL ON
8 = AUTO ON,
24 h / day
172 Operating mode
when terminals H1–
M are linked
0
(0…9)
.........................
9 =
NORMAL ON,
24 h / day