Building Technologies 74 319 0618 0 a 17.04.2008 60/276
en
196 Identification code
of room unit
Display function
Block “Solar d.h.w.“
201 Temperature differ-
ential ON solar
8 °C
(0…40)
...................
°C
Temperature differential be-
tween collector and storage
tank
202 Temperature differ-
ential OFF solar
4 °C
(0…40)
...................
°C
Temperature differential be-
tween collector and storage
tank
203 Collector frost pro-
tection
--- °C
(--- / –20…5)
...................
°C
Setting --- = No collector frost
protection
204
Collector over tem-
perature protection
105 °C
(--- / 30…260)
...................
°C
Setting --- = No collector over
temperature protection
205
Evaporation heat
carrier
140 °C
(--- / 60…260)
...................
°C
Setting --- = No collector pump
protection
206
D.h.w. charging
temperature maxi-
mum limitation
80 °C
(8…100)
...................
°C
207
D.h.w. storage tank
temperature maxi-
mum limitation
90 °C
(8…100)
...................
°C
No safety function
208 Collector start func-
tion gradient
--- min/°C
(--- / 1…20)
...........
min/°C
Setting --- = Function deacti-
vated