Siemens Building Technologies CE1B2540en 74 319 0616 0 b 18.07.2008 29/32
If the controller uses a room temperature sensor
(room unit):
Is the sensor affected by drafts, direct solar radiation,
etc.?
Is the sensor affected by heat gains, such as people,
machines, lighting, etc.?
Is the sensor covered by furniture, curtains, etc.?
Are all thermostatic radiator valves in the "sensor's
room" in the fully open position?
The control no longer works:
If the heat source and the heating
circuit pumps still operate: Press button
A to switch to manual operation:
2540Z06
Heating plant with a valve:
The valve can be operated manually by pressing but-
ton B (OPENING) or C (CLOSING)
Heating plant with no valve:
The burner runs continuously. With two-stage burners,