Power Modules
4.3 Power Modules Blocksize (PM340)
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
149
PM340 with integrated line filter
Max. cable length
to braking resistor
m 15 15 15
Screw terminals for
cable cross-sections 1.0 … 6 mm
2
DC link connection, connection for
braking resistor
DCP/R1, DCN, R2
3)
Rated power of a typical standard induction motor at 400 V 3 AC
The input cur
rent depends on the motor load and line impedance. The input currents apply for a load with the type rating
(based on I
rated
) for a line impedance corresponding to u
k
= 1%.
Max. motor cable length 25 m (shielded) for PM340 Power Modules with integrated line filter to maintain the limit values
of EN 61800-3 Category C2.
Table 4- 26 Technical data of the PM340, FSC (380 V ... 480 V 3 AC ±10 %)
PM340 with integrated line filter
Rated current I
n
Base-load current I
H
for S6 operation (40 %) l
s6
max
A
A
A
18
14
19,6
25
21
27,8
32
27
37,1
1)
on basis of I
n
kW
7,5
11
15
3
Sound pressure level L
pA
(1 m)
2)
with/without integrated line reactor
Rated current
Short-circuit current rating
SCCR
A
kA
25
65
35
65
45
65