Power Modules
4.4 Power Modules Chassis
AC Drive
176 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Derating for Chassis Power Modules
For further information, see Section Derating as a function of the ambient temperature, pulse
frequency, and installation altitude (Page 37).
Table 4- 39 Current derating for chassis units as a function of ambient temperature (supply air temperature at the air inlet
of the chassis unit) and installation altitude
Installation altitude
above sea level in m
Current derating factor (in % of rated current)
at an ambient temperature (air intake temperature) of
The values apply under the precondition that a cooling air flow though the units as stated in
the technical data is ensured.
Table 4- 40 Derating factor of the output current as a function of the pulse frequency
Output current for a
pulse frequency of 2 kHz
[A]
Derating factor for a
pulse frequency of 4 kHz
Derating factor for a
pulse frequency of 8 kHz
By multiplying the rated pulse frequency with a multiple integer, the following output
frequencies can be achieved taking into account the derating factors:
Table 4- 41 Maximum output frequencies achieved by increasing the pulse frequency in VECTOR
mode
Maximum output frequency [Hz]
1)
1)
The maximum output frequency is limited to 300 Hz due to the closed-loop control (see SINAMICS