Motor-side power components
6.1 Blocksize
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
221
Note
The motor reactor must be mounted as close as possible to the Power Module.
Installation of motor reactors for PM240-2 Power Modules
The motor reactors for PM240-2 Power Modules of frame sizes FSA to FSC are designed for
installation in a cabinet. The motor reactor is installed on the mounting surface next to the
Power Module.
Table 6- 6 Mounting of motor reactors for PM240-2 Power Modules
FSA
4 x M4 screws
4 x M4 nuts
3 Nm
4 x M5 screws
4 x M5 nuts
5 Nm
FSC