Motor-side power components
6.2 Chassis
AC Drive
246 Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Table 6- 25 Technical data, dV/dt filter plus Voltage Peak Limiter
Suitable for Power Module (unit
rating)
6SL3310- 1TE32-1AAx (110 kW)
1TE32-6AAx (132 kW)
1TE33-1AAx (160 kW)
1TE33-8AAx (200 kW)
Power loss
- at 50 Hz
- at 60 Hz
kW
kW
0,701
0,729
0,874
0,904
Connections
- to the Power Module
- load
M10
M10
M12
M12
Max. permissible
cable length between dV/dt
m 300 (shielded)
450 (unshielded)
Dimensions
Width
Height
mm
mm
410
370
460
370
Power loss
- at 50 Hz
- at 60 Hz
kW
kW
0,029
0,027
0,042
0,039
Connections
- to the dV/dt reactor
- DC
M8
M8
Terminal 70 mm²
Terminal 70 mm²
Dimensions
Width
Height
mm
mm
265
263
392
285