Supplementary system components and encoder system integration
8.3 Safe Brake Adapter optional module
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
387
X11 interface to the Control Interface Module
Table 8- 25 X11 interface to the Control Interface Module
Connection to Control Interface Board, X46.1
Connection to Control Interface Board, X46.2
Connection to Control Interface Board, X46.3
Ground of the relay feedback signal
Connection to Control Interface Board, X46.4
X11.5 P24 P24 of the auxiliary voltage to supply the
Connection to Control Interface Board, X42.2
Ground of the auxiliary voltage
Connection to Control Interface Board, X42.3
Max. connectable cross-section: 2.5 mm
2
Fire hazard due to overheating when permissible cable lengths are exceeded
Excessively long power cables can cause overheating of components with resulting fire and
smoke development.
• The maximum permissible cable length of 10 m between the 230 V AC Safe Brake
Adapter and the Control Interface module must not be exceeded.
Use the cable harness (length: 4 m) order no. 6SL3060-4DX04-0AA0.
X12 230 V AC power supply
Table 8- 26 X12 230 V AC power supply
Supply voltage: AC 230 V
Current consumption: 2 A
Max. connectable cross-section: 2.5 mm
2