Installation, connecting up, commissioning
3.3 Installing, connecting and commissioning
SIMATIC CM 1242-5
20 Operating Instructions, 01/2023, C79000-G8976-C245-06
WARNING
Insufficient isolation of intrinsically safe and non-intrinsically safe circuits
Risk of explosion in hazardous areas
When connecting intrinsically safe and non-intrinsically safe circuits, ensure that the
galvanic isolation is performed properly in compliance with local regulations (e.g. IEC
60079-14).
Observe the device approvals applicable for your country.
WARNING
Unauthorized repair of devices in explosion-proof design
Risk of explosion in hazardous areas
Repair work may only be performed by personnel authorized by Siemens.
3.3 Installing, connecting and commissioning
NOTICE
Improper mounting
Improper mounting may damage the device or impair its operation.
Before mounting the device, always ensure that there is no visible damage to the device.
Mount the device using suitable tools. Observe the information in the respective section
about mounting.
WARNING
Open equipment
The devices are "open equipment" acc. to the standard IEC 61010-2-201 or UL 61010-2-201
/ CSA C22.2 No. 61010-2-201. To fulfill requirements for safe operation with regard to
mechanical stability, flame retardation, stability, and protection against contact, the
following alternative types of installation are specified:
Installation in a suitable cabinet.
Installation in a suitable enclosure.
Installation in a suitably equipped, enclosed control room.