EasyManua.ls Logo

Siemens S7-1200 - Page 207

Siemens S7-1200
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic instructions
7.1 Bit logic operations
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
207
Set and Reset Bit Field
Table 7- 10 SET_BF and RESET_BF instructions
LAD
1
FBD
SCL
Description
Not available Set bit field:
When SET_BF is activated, a data value of 1 is assigned to "n"
bits starting at address tag OUT. When SET_BF is not
activated, OUT is not changed.
Not available Reset bit field:
RESET_BF writes a data value of 0 to "n" bits starting at
address tag OUT. When RESET_BF is not activated, OUT is
not changed.
1
For LAD and FBD: These instructions must be the right-most instruction in a branch.
2
For SCL: You must write code to replicate this function within your application.
Table 7- 11 Data types for the parameters
Parameter
Data type
Description
OUT Bool Starting element of a bit field to be set or reset (Example:
#MyArray[3])
n
Constant (UInt)
Number of bits to write
Set-dominant and Reset-dominant flip-flops
Table 7- 12 RS and SR instructions
LAD / FBD
SCL
Description
Not available Reset/set flip-flop:
RS is a set dominant latch where the set dominates. If the set (S1) and reset (R)
signals are both true, the value at address INOUT will be 1.
Not available Set/reset flip-flop:
SR is a reset dominant latch where the reset dominates. If the set (S) and reset
(R1) signals are both true, the value at address INOUT will be 0.
1
For LAD and FBD: These instructions must be the right-most instruction in a branch.
2
For SCL: You must write code to replicate this function within your application.

Table of Contents

Other manuals for Siemens S7-1200

Related product manuals