Extended instructions
8.3 Distributed I/O (PROFINET, PROFIBUS, or AS-i)
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
323
Error_decode
(B#16#....)
Error_code_1
(B#16#....)
Explanation (DVP1)
Description
96 The "RALRM (Page 318)" cannot supply the OB start
information, management information, header
information, or additional interrupt information.
For the following OBs, you can use the "DPNRM_DG
(Page 328)" instruction to read the current diagnostics
message frame of the relevant DP slave asynchronously
(address information from OB start information):
Hardware interrupt (Page 87)
Status (Page 93), Update (Page 93) or Profile
(Page 94)
Diagnostic error interrupt (Page 89)
Pull or plug of modules (Page 91)
A0 Read error Negative acknowledgement while reading from the
module
A1
Write error
Negative acknowledgement while writing to the module
A2 Module failure DP protocol error at layer 2 (for example, slave failure or
bus problems)
A3 Reserved, pass
PROFIBUS DP: DP protocol error with Direct-Data-
Link-Mapper or User-Interface/User
PROFINET IO: General CM error
A4
Reserved, pass
Communication on the communication bus disrupted
A5
Reserved, pass
-
A7
Reserved, pass
DP slave or modules is occupied (temporary error).
A8 Version conflict DP slave or module reports non-compatible versions.
A9
Feature not supported
Feature not supported by DP slave or module
AA to AF User specific DP slave or module reports a manufacturer-specific error
in its application. Please check the documentation from
the manufacturer of the DP slave or module.
B0 Invalid index Data record not known in module; illegal data record
number ≥ 256
B1 Write length error The length information in the RECORD parameter is
incorrect.
With "RALRM": Length error in AINFO
Note
: Refer to the online information system of
STEP 7 for immediate access to information on how
to interpret the "AINFO" returned buffers.
With "RDREC (Page 315)" and "WRREC
(Page 315)": Length error in "MLEN"
B2
Invalid slot
The configured slot is not occupied.
B3 Type conflict Actual module type does not match specified module
type.
B4
Invalid area
DP slave or module reports access to an invalid area.
B5
Status conflict
DP slave or module not ready
B6
Access denied
DP slave or module denies access.