Extended instructions
8.3 Distributed I/O (PROFINET, PROFIBUS, or AS-i)
S7-1200 Programmable controller
330 System Manual, 03/2014, A5E02486680-AG
Error code
Description
Restriction
80A4 Communication problem on the communication bus
The error occurs between the
CPU and the external DP
interface module.
80B0
The instruction is not possible for module type.
The module does not recognize the data record.
Data record number 241 is not permitted.
-
80B1 The length specified in the RECORD parameter is incorrect. Specified length > record
length
80B2
The configured slot is not occupied.
-
80B3
Actual module type does not match the required module type.
-
80C0
There is no diagnostic information.
-
80C1 The data of the previous write job for the same data record on the module
have not yet been processed by the module.
-
80C2 The module is currently processing the maximum possible number of jobs
for a CPU.
-
80C3
The required resources (memory, etc.) are currently occupied.
-
80C4 Internal temporary error. The job could not be processed.
Repeat the job. If this error occurs frequently, check your system for
electrical disturbance sources.
-
80C5 Distributed I/Os not available Distributed I/Os
80C6 Data record transfer was stopped due to a priority class abort (restart or
background)
Distributed I/Os
8xyy
1
General error codes
Refer to "Extended instructions, Distributed I/O: Error information for RDREC, WRREC, and
RALRM" (Page 322) for more information on general error codes.