Extended instructions
8.5 Diagnostics (PROFINET or PROFIBUS)
S7-1200 Programmable controller
350 System Manual, 03/2014, A5E02486680-AG
Table 8- 122 Example 2: A module has been pulled from PROFIBUS slave device "DPSlave_12". A
value of 0x0110_0000 is returned for MODE 2 (Device defective).
Bit 0 is true; data is available.
vice 12 (Bit 12) is marked as defective.
MODE 5 (Problem in device) returns the same information as MODE 2 (Device defective).
Table 8- 123 Example 2 (continued): A module has been pulled from PROFIBUS slave device
"DPSlave_12". A value of 0x01FC_FF03 is returned for MODE 4 (Device exists).
Bit 0 is true; data is available.
Even though device 12 (Bit 12) has an error as shown in MODE 2 (Device defective) above, the
device is still functioning on the network which causes MODE 4 (Device exists) to show the device
Table 8- 124 Example 3: PROFIBUS slave device "DPSlave_12" is disconnected (cable disconnected
or power loss) from the PROFIBUS network. "DPSlave_12" is still detected as a
defective device as well as an error in the device. The difference is that "DPSlave_12" is
no longer detected as a device that exists. A value of 0x01EC_FF03 is returned for
MODE 4 (Device exists).
Bit 0 is true; data is available.
Byte 3 0xFF Bit 23 1111-1111 Bit 16
Device 12 (Bit 12) is marked as not existing. With this exception, devices 10 through 25 still report as
existing.