Extended instructions
8.5 Diagnostics (PROFINET or PROFIBUS)
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
355
Example 1:
Normal operation with
no errors
Example 2:
PROFIBUS slave
device DPSlave_12
module pulled
Example 3:
PROFIBUS slave
device DPSlave_12
disconnected
1: Module configuration
0x1F00_0000 0x1F00_0000 0x1F00_0000
The following four tables show a binary breakdown of the four bytes of data that are being
analyzed:
Table 8- 132 Example 1: No errors: A value of 0x1F00_0000 is returned for MODE 1 (Module
configuration active).
Bit 0 is true; data is available.
Slots 1 (Bit 1) through 4 (Bi
t 4) contain modules. Slots 5 (Bit 5) and beyond do not contain modules..
MODE 4 (Module exists) data matches MODE 1 (Module configuration active), so the configured
modules match the existing modules.
Table 8- 133 Example 2: A module has been pulled from PROFIBUS slave device "DPSlave_12". A
value of 0x0900_0000 is returned for MODE 2 (Module defective).
Bit 0 is true; data is available.
Only module 3 (Bit 3) is marked as defective. All other modules are functional.