Extended instructions
8.5 Diagnostics (PROFINET or PROFIBUS)
S7-1200 Programmable controller
356 System Manual, 03/2014, A5E02486680-AG
Table 8- 134 Example 2 (continued): A module has been pulled from PROFIBUS slave device
"DPSlave_12". A value of 0x1700_0000 is returned for MODE 4 (Module exists).
Bit 0 is true; data is available.
Module 3 (Bit 3) is shown as missing. Modules 1, 2, and 4 (Bits 1, 2, and 4) are shown as existing.
Table 8- 135 Example 3: PROFIBUS slave device "DPSlave_12" is disconnected (cable disconnected
or power loss) from the PROFIBUS network. A value of 0x1F00_0000 is returned for
MODE 2 (Module defective).
Bit 0 is true; data is available.
The modules in slots 1 through 4 (Bits 1 through 4) are all marked as defective
since the device is
missing.
MODE 5 (Problem in module) shows the same information as MODE 2 (Module defective).
The PROFINET example consists of the following:
● 16 PROFINET slave devices named "et200s_1" through "et200s_16"
● The 16 PROFINET devices use PROFINET device numbers 1 through 16, respectively.
● Each slave device is configured with multiple I/O modules.
● The example uses PROFINET slave "et200s_1" which contains a head module, a power
module, and 18 I/O modules.
● The first four bytes of the returned STATE parameter information is displayed.
Example 1:
Normal operation with
no errors
Example 2:
PROFINET et200s_1
slave module pulled
Example 3:
PROFINET et200s_1
slave disconnected
1: Module configuration
0xFFFF_1F00 0xFFFF_1F00 0xFFFF_1F00
5: Problem in module 0x0000_0000 0x0180_0000 0xFFFF_1F00