Communication
10.2 PROFINET
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
543
ERROR
STATUS
(DW#16#...)
Description
0
00700200
Intermediate call (REQ irrelevant)
1
C08xyy00
General failure
1
C0808000
LADDR parameters for identification of the interface are invalid.
1 C0808100 LADDR parameters for identification of the interface have been assigned a non-
supported hardware interface.
1 C0808200
CONF_DATA parameter error: Data type of the Variant pointer does not match the data
type Byte.
1
C0808300
CONF_DATA parameter error: The area pointer is not in the DB of the Variant pointer.
1
C0808400
CONF_DATA parameter error: The Variant pointer is the wrong length.
1
C0808600
Reserved
1
C0808700
Inconsistency in the CONF_DATA data block length to the IP configuration
1 C0808800 The parameters of the CONF_DATA data block field_type_id are invalid. (Only
field_type_id = 0 is allowed.)
1 C0808900 The parameters of the CONF_DATA data block field_type_id are invalid or have been
used several times.
1
C0808A00
LEN length of the IP configuration parameters or subfield_cnt errors
1 C0808B00 The IP configuration ID parameter is invalid or unsupported.
1 C0808C00 The Sub-block of the IP configuration is incorrectly placed (Sub-block wrong, wrong
order, or used multiple times).
1 C0808D00 The length of a statement LEN Sub-blocks is invalid.
1
C0808E00
The value of the parameter in Sub-blocks mode is invalid.
1
C0808F00
Sub-block conflict between the IP configuration and a previous Sub-block.
1 C0809000 The parameters of the subfield are write-protected (for example: parameters are
specified by configuration, or PNIO mode is enabled).
1
C0809100
Reserved
1 C0809400 A parameter in the Sub-block IP configuration has not been defined or may not be
used.
1 C0809500 There is an inconsistency between a parameter of the Sub-block IP configuration and
other parameters.
1 C080C200 Instruction cannot be executed. This error can occur if, for example, communication
with the interface has been lost.
1 C080C300 There are not enough resources. This error can occur if, for example, the instruction is
called multiple times with different parameters
1 C080C400 Communication failure. The error can occur temporarily and will require a repeat of the
user program.
1
C080D200
Execution of the instruction is not supported by the PROFINET interface.