Communication processor and Modbus TCP
12.3 Point-to-point (PtP) communication
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
685
Note
The DONE, NDR, and ERROR parameters are set for one execution only. Your program
logic must save temporary output state va
lues in data latches, so you can detect state
changes in subsequent program scans.
Table 12- 5 Common condition codes
Function is busy with the first call.
Function is busy with subsequent calls (polls after the first call).
Illegal pointer in parameter x
All internal instance memory in use, too many concurrent instructions in progress
Timeout, module error, or other internal error
Parameterization failed because parameterization is in progress in background.
8083 Buffer overflow:
The CM or CB returned a received message with a length greater than the length parameter
Internal error: Wrong message length, wrong submodule, or illegal message
Internal error: Wrong version in parameterization message
Internal error: Wrong record length in parameterization message
Table 12- 6 Common error classes
Used to define common port configuration errors
Used to define common transmit configuration errors
Used to define common receive configuration errors
Used to define common transmission runtime errors
Used to define common reception runtime errors
Signal handling 80Fx Used to define common errors associated with all signal