Technical specifications
A.2 CPU 1211C
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
841
Table A- 17 Digital outputs
CPU 1211C AC/DC/Relay and
CPU 1211C DC/DC/Relay
Number of outputs 4 4
Solid state - MOSFET (sourcing)
5 to 30 VDC or 5 to 250 VAC
Logic 1 signal at max. current
Logic 0 signal with 10 KΩ load
Leakage current per point
Isolation (field side to logic) 1500 VAC for 1 minute
(coil to contact)
500 VAC for 1 minute
Isolation between open contacts
L+ minus 48 VDC, 1 W dissipation
Maximum relay switching frequency
Switching delay (Qa.0 to Qa.3) 10 ms max. 1.0 μs max., off to on
Pulse Train Output rate Not recommended
1
100 kHz (Qa.0 to Qa.3)
2
, 2 Hz min.
Lifetime mechanical (no load)
10,000,000 open/close cycles
Lifetime contacts at rated load
100,000 open/close cycles
Behavior on RUN to STOP Last value or substitute value
Last value or substitute value
Number of outputs on simultaneously
4 at 60 °C horizontal, 50 °C vertical
Cable length (meters) 500 m shielded,
500 m shielded,
For CPU models with relay outputs, you must install a digital signal board (SB) to use the pulse outputs.
Depending on your pulse receiver and cable, an additional load resistor (at least 10% of rated current) may improve
pulse signal quality and noise immunity.