Technical specifications
A.3 CPU 1212C
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
847
A.3
CPU 1212C
A.3.1
General specifications and features
Table A- 28 General
Technical data
CPU 1212C
AC/DC/Relay
CPU 1212C
DC/DC/Relay
CPU 1212C
DC/DC/DC
Order number
6ES7 212-1BE40-0XB0
6ES7 212-1HE40-0XB0
6ES7 212-1AE40-0XB0
Dimensions W x H x D (mm)
90 x 100 x 75
90 x 100 x 75
90 x 100 x 75
Shipping weight
425 grams
385 grams
370 grams
Power dissipation
11 W
9 W
9 W
Current available
(SM and CM bus)
1000 mA max.
(5 VDC)
1000 mA max.
(5 VDC)
1000 mA max.
(5 VDC)
Current available (24 VDC) 300 mA max.
(sensor power)
300 mA max.
(sensor power)
300 mA max.
(sensor power)
Digital input current consumption
(24 VDC)
4 mA/input used 4 mA/input used 4 mA/input used
Table A- 29 CPU features
Technical data
Description
User memory
Work
50 Kbytes
Load
1 Mbyte internal, expandable up to SD card size
Retentive
10 Kbytes
On-board digital I/O
8 inputs/6 outputs
On-board analog I/O
2 inputs
Process image size
1024 bytes of inputs (I)/1024 bytes of outputs (Q)
Bit memory (M) 4096 bytes
Temporary (local) memory
16 Kbytes for startup and program cycle (including associated FBs and FCs)
6 Kbytes for each of the other interrupt priority levels (including FBs and FCs)
Signal modules expansion
2 SMs max.
SB, CB, BB expansion 1 max.
Communication module expansion 3 CMs max.
High-speed counters Up to 6 configured to use any built-in or SB inputs. See table, CPU 1212C: HSC
default address assignments (Page 411)
100/
1
80 kHz (Ia.0 to Ia.5)
30 /
1
20 kHz (Ia.6 to Ia.7)
Pulse outputs
2
Up to 4 configured to use any built-in or SB outputs
100 kHz (Qa.0 to Qa.3)
30 kHz (Qa.4 to Qa.5)