Table A- 70 Communication
Connections
• 8 for Open User Communication (active or passive): TSEND_C,
TRCV_C, TCON, TDISCON, TSEND, and TRCV
• 3 for server GET/PUT (CPU-to-CPU) S7 communication
• 8 for client GET/PUT (CPU-to-CPU) S7 communication
Isolation (external signal to PLC logic)
Transformer isolated, 1500 VAC, for short term event safety only
Table A- 71 Power supply
Input current
(max. load)
CPU only 100 mA at 120 VAC
500 mA at 24 VDC
CPU with all expansion
300 mA at 120 VAC
1500 mA at 24 VDC
Isolation (input power to logic)
Ground leakage, AC line to functional
earth
0.5 mA max. -
Hold up time (loss of power) 20 ms at 120 VAC
80 ms at 240 VAC
10 ms at 24 VDC
Internal fuse, not user replaceable 3 A, 250 V, slow blow
Table A- 72 Sensor power
Output current rating (max.)
400 mA (short-circuit protected)
Maximum ripple noise (<10 MHz)
Isolation (CPU logic to sensor power)