EasyManua.ls Logo

Siemens S7-1200 - Step Response of Built-In Analog Inputs of the CPU; Sample Time for the Built-In Analog Ports of the CPU; Measurement Ranges of the Analog Inputs for Voltage (Cpus)

Siemens S7-1200
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
A.5 CPU 1215C
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
873
Technical data
Description
Accuracy (25 °C / 0 to 55 °C)
3.0% / 3.5% of full-scale
Cable length (meters)
100 m, shielded twisted pair
A.5.4.1
Step response of built-in analog inputs of the CPU
Table A- 76 Step Response (ms), 0 V to 10 V measured at 95%
Smoothing selection (sample averaging)
Rejection frequency (Integration time)
60 Hz
50 Hz
10 Hz
None (1 cycle): No averaging
50 ms
50 ms
100 ms
Weak (4 cycles): 4 samples
60ms
70 ms
200 ms
Medium (16 cycles): 16 samples
200 ms
240 ms
1150 ms
Strong (32 cycles): 32 samples
400 ms
480 ms
2300 ms
Sample time
4.17 ms
5 ms
25 ms
A.5.4.2
Sample time for the built-in analog ports of the CPU
Table A- 77 Sample time for built-in analog inputs of the CPU
Rejection frequency (Integration time selection)
Sample time
60 Hz (16.6 ms)
4.17 ms
50 Hz (20 ms)
5 ms
10 Hz (100 ms)
25 ms
A.5.4.3
Measurement ranges of the analog inputs for voltage (CPUs)
Table A- 78 Analog input representation for voltage (CPUs)
System
Voltage Measuring Range
Decimal
Hexadecimal
0 to 10 V
32767
7FFF
11.851 V
Overflow
32512
7F00
32511
7EFF
11.759 V
Overshoot range
27649
6C01
27648
6C00
10 V
Rated range
20736
5100
7.5 V
34
22
12 mV
0
0
0 V
Negative values Negative values are not
supported

Table of Contents

Other manuals for Siemens S7-1200

Related product manuals