Technical specifications
A.6 CPU 1217C
S7-1200 Programmable controller
884 System Manual, 03/2014, A5E02486680-AG
Isolation (field side to logic)
500 VAC for 1 minute (functional isolation)
L+ minus 48 VDC, 1 W dissipation
Switching delay (Qa.0 to Qa.3) 1.0 μs max., off to on
Switching delay (Qa.4 to Qb.1) 50 μs max., off to on
Maximum relay switching frequency
Pulse Train Output rate
100 KHz max. (Qa.4 to Qb.1)
1
, 2 Hz min.
Type: 1.5 V Differential output
Qa.0 to Qa.3 (.0+ 0- to .3+ .3-)
Common mode voltage range
-7 V to +12 V, 1 second, 3 VRMS continuous (RS485 characteristics)
Transmitter differential output voltage
2 V min. at RL = 100 Ω, 1.5 V min. at RL = 54 Ω
100 Ω between Qa'+' and Qa'-'
100 Ω including termination
500 VAC, 1 minute (functional isolation)
Switching delay (DQa.0 to DQa.3)
Differential output channel-to-channel
40 ns max.
1 MHz (Qa.0 to Qa.3), 2 Hz min.
General specifications
(all digital outputs)
Last value or substitute value (default value 0)
Number of outputs on simultaneously 3 Solid state - MOSFET (sourcing) outputs (no adjacent points) and 4 differential
outputs at 60 °C horizontal or 50 °C vertical
10 at 55 °C horizontal or 45 °C vertical
500 m shielded, 150 m unshielded
Depending on your pulse receiver and cable, an additional load resistor (at least 10% of rated current) may improve
pulse signal quality and noise immunity.