Technical specifications
A.9 Thermocouple and RTD signal modules (SMs)
S7-1200 Programmable controller
928 System Manual, 03/2014, A5E02486680-AG
Note
The RTD unused channels can be deactivated. No erro
r will occur if an unused channel is
The RTD module needs to have the current loop continuous to eliminate extra stabilization
time which is automatically added to an unused channel that is not deactivated. For
consistency the RTD module shoul
d have a resistor connected (like the 2-wire RTD
Selection tables for the SM 1231 RTD
Table A- 178 Ranges and accuracy for the different sensors supported by the RTD modules
Normal
range
accuracy
@ 25 °C
Normal range
accuracy
-20 °C to
60 °C
Pt 0.003850
ITS90
DIN EN 60751
Pt 100
-145.00 °C -120.00 °C 145.00 °C 155.00 °
±0.20 °C ±0.40 °C
Pt 10 -243.0 °C -200.0 °C 850.0 °C 1000.0 °
±1.0 °C ±2.0 °C
-243.0 °C -200.0 °C 850.0 °C 1000.0 °
C
±0.5 °C ±1.0 °C
Pt 1000
Pt 0.003902
Pt 0.003916
Pt 0.003920
Pt 100 -243.0 °C -200.0 °C 850.0 °C 1000.0 °
± 0.5 °C ±1.0 °C
-243.0 °C -200.0 °C 850.0 °C 1000.0 °
C
± 0.5 °C ±1.0 °C
Pt 0.003910
-273.2 °C -240.0 °C 1100.0 °C 1295 °C ±0.8 °C ±1.6 °C