Technical specifications
A.14 Communication interfaces
S7-1200 Programmable controller
System Manual, 03/2014, A5E02486680-AG
977
Isolation
RS485 signal to chassis ground
RS485 signal to CPU logic common
500 VAC, 1 minute
1000 m max. (baud rate dependent)
Baud rate 300 baud, 600 baud, 1.2 kbits, 2.4 kbits, 4.8 kbits, 9.6 kbits (default),
19.2 kbits, 38.4 kbits, 57.6 kbits, 76.8 kbits, 115.2 kbits,
Parity No parity (default), even, odd, Mark (parity bit always set to 1),
Space (parity bit always set to 0)
XON/XOFF supported for the RS422 mode
Table A- 255 Power supply
Table A- 256 RS485 or RS422 connector (female)
Logic or communication ground
+5 V with 100 ohm series resistor: Output
2 TxD+
1
Connected for RS422
Not used for RS485: Output
7 Not connected
3 TxD+ Signal B (RxD/TxD+): Input/Output 8 TXD- Signal A (RxD/TxD-): Input/Output
4 RTS
2
Request to send (TTL level) Output 9 TXD-
1
Connected for RS422
Not used for RS485: Output
5 GND Logic or communication ground SHELL Chassis ground
Pins 2 and 9 are only used as transmit signals for RS422.
The RTS is a TTL level signal and can be used to control another half duplex device based on this signal. It is active
when you transmit and is inactive all other times.