6 LCCF_EnetScanner block
EtherNet/IP Scanner
Entry-ID: 109782314, V1.1.0, 04/2021
40
© Siemens AG
2021 All rights reserved
Valid
Busy
Error
Status
Code
(in hex)
Cause
Remedy
smaller than
configured for
adapter[x]
size.
FALSE
FALSE
TRUE
16#82x8
Parameterized
output buffer is
smaller than
configured for
adapter[x]
Adjust the configured
OT direction data
size.
FALSE
FALSE
TRUE
16#82x9
Parameterized
configuration data
buffer is smaller
than configured
for adapter[x]
Adjust the configured
configuration data size.
FALSE
FALSE
TRUE
16#86xA
Incompatible
buffer types for
adapter [x]
The configured TO
buffer type is
incompatible to the
parameterized Input
buffer type.
Adjust both the size
and type either of the
configuration or for the
parameterized buffer.
FALSE
FALSE
TRUE
16#86xB
Incompatible
buffer types for
adapter [x]
The configured OT
buffer type is
incompatible to the
parameterized Output
buffer type.
Adjust both the size
and type either of the
configuration or for the
parameterized buffer.
FALSE
FALSE
TRUE
16#86xC
Incompatible
buffer types for
adapter [x]
The configured
configuration data
buffer type is
incompatible to the
parameterized
configuration data
buffer type.
Adjust both the size
and type either of the
configuration or for the
parameterized buffer.