6 LCCF_EnetScanner block
EtherNet/IP Scanner
Entry-ID: 109782314, V1.1.0, 04/2021
41
© Siemens AG
2021 All rights reserved
6.1.2 Technical data
For better planning of the automation program the user must be aware, that the
operation of the LCCF_EnetScanner block has impacts on both memory loading
and cycle time of the remaining automation program.
As all the protocol handling is done as part of the user program, the cycle time will
be extended by the time the selected CPU model requires to execute the protocol
stack. As one could imagine the more adapters are configured the more time is
necessary to compute the communications. Another performance influencing factor
is the RPI. The shorter the RPI is, the more often communication to the adapters
need to be done.
Figure 6-1: PLC load depending on RPI and number of adapters
NOTE
The above diagram doesn’t show real loadings nor do the value are based on
real measurements for a specific CPU.
The diagram only illustrates the loading dependencies.
As shown in the above diagram, lower RPI cause more updates per time unit. This
in turn causes a higher load o the PLC. The number of configured adapters also
has an influence on the PLC load in the way, that the higher the number is, the
higher the load will be (proportional).