EtherNet/IP Scanner
Entry-ID: 109782314, V1.1.0, 04/2021
© Siemens AG
2021 All rights reserved
SIMATIC S7-1500
The average load shown in the below table are based on measurements taken on
a CPU 1512C used throughout the application example loaded with the two
adapters.
Table 6-5: Execution times for LCCF_EnetScanner
The measured load is based on a 10ms cyclic interrupt and the data exchange
configured in the application example.
Table 6-6: configured data exchange sizes
Besides program execution time memory consumption should be taken into
consideration, when selecting the CPU model for a specific automation task. The
LCCF_EnetScanner block contributes to the memory loading a certain amount of
memory plus the data required per configured adapter. The following tables will
provide the detailed information.
Table 6-7: Memory consumption S7-1500
Memory is also consumed for each adapter configured and data areas to be
provided for it.
Table 6-8: Memory consumption for EtherNet/IP IO system
With the SIMATIC S7-1500 up to 16 EtherNet/IP adapters can be controlled.
This limitation is a compromise between many factors such as update rates,
CPU load, memory consumption and others.
If a specific application requires more the S7-1500 allows for more OUC
connection resources, which can be used.